Quality & Inspections · Mandatory · Construction
Pressure Test Record
A record of pressure testing on pipework systems including heating, gas, and water installations.
Last reviewed: 29 March 2026 — This guide reflects UK law as of this date. BS EN 806 / Gas Safety Regs remains current with no amendments enacted as of 29 March 2026. Next scheduled review: 29 March 2027.
| Legal basis | BS EN 806 (water systems) + Gas Safety (Installation and Use) Regulations 1998 (gas systems) + WRAS (Water Regulations Advisory Scheme) |
| Why pressure test | Verifies leak-tight integrity before insulation, burial, or commissioning — the last opportunity to detect defects while joints remain accessible |
| Water systems | Test at 1.5× maximum working pressure, hold for a minimum of 1 hour, no pressure drop acceptable |
| Gas systems | Tightness testing is mandatory before any appliance connection — must be carried out by a Gas Safe registered engineer only |
| WRAS | All fittings in contact with drinking water must be WRAS approved to confirm no contamination of the wholesome supply |
1. Pressure Testing — The Last Chance to Find Leaks Before Concealment
The pressure test is the quality gate between pipework installation and concealment or commissioning. It is the definitive confirmation that every joint, fitting, and length of pipework is leak-tight at a pressure above normal service conditions. Once pipework is insulated, buried, or enclosed in walls, floors, or ceilings, finding and repairing a leak becomes enormously disruptive and costly.
For water systems, testing is governed by BS EN 806 and the Water Supply (Water Fittings) Regulations. The test pressure is typically 1.5 times the maximum working pressure, held for a minimum of one hour with no measurable pressure drop. For gas systems, tightness testing is a mandatory requirement under the Gas Safety (Installation and Use) Regulations 1998 and must be performed by a Gas Safe registered engineer in accordance with IGEM/UP/1C. The test method, medium, and acceptance criteria differ between water and gas — and the consequences of failure in either case can be severe.
The pressure test record captures every detail of the test: the system tested, the test medium, the pressures applied, the hold period, visual inspection findings, and the identity of the tester and witness. Without a complete and signed record, there is no evidence that the test was carried out correctly — or at all.
Never conceal untested pipework
Never conceal pipework that has not been pressure tested and signed off — finding leaks after concealment is enormously costly. Insulation, plasterboard, screed, and backfill must not proceed until the test record is complete.
2. Pressure Test Record Fields
The following table sets out the fields that must be captured on a pressure test record. Each field serves a specific purpose in demonstrating that the test was correctly planned, executed, and witnessed.
| Field | Description |
|---|---|
| Project/system | Identifies the project and the specific system or section under test |
| Date | Date of the pressure test |
| System type | Domestic cold water, hot water, LTHW heating, gas, CHW, fire suppression, etc. |
| Test medium | Water, air, or inert gas — must match specification and standard requirements |
| Working pressure | Maximum normal operating pressure of the system (bar) |
| Test pressure | Pressure applied during the test — typically 1.5× working pressure for water systems |
| Pressure source | Manual pump, electric pump, or mains supply used to pressurise the system |
| Pre-test checks | Air purged, system filled, sensitive instruments isolated, all joints accessible |
| Test start | Time and pressure reading at the start of the hold period |
| Hold period | Duration of the hold period — minimum 1 hour for water systems |
| Pressure at end | Pressure reading at the end of the hold period |
| Visual inspection | Confirmation that all accessible joints were visually inspected during and after the hold |
| Result | Pass or fail, with comments on any anomalies observed |
| Tested by | Name, signature, and qualifications of the person who conducted the test |
| Witnessed by | Name and signature of the witness (client representative, clerk of works, or engineer) |
3. Common Mistakes
Concealing pipework before testing
Insulation, plasterboard, screed, or backfill applied before the pressure test has been completed and signed off. Once concealed, any leak requires destructive investigation to locate and repair — at significant cost and programme delay.
Air testing where water testing is required
Some specifications and standards require hydraulic (water) testing, not pneumatic (air) testing. Air testing of certain systems may not detect small leaks that a hydraulic test would reveal. Always check the applicable standard and specification before selecting the test medium.
Using an uncalibrated gauge
A pressure gauge that has not been calibrated within its certification period renders the test result unverifiable. Calibration certificates must be current and retained alongside the test record as evidence of gauge accuracy.
Not isolating sensitive instruments before pressurising
Pressure relief valves, expansion vessels, and sensitive instrumentation must be isolated before the system is pressurised to test pressure. Failure to isolate can damage components rated for normal operating pressure only.
Gas testing by a non-Gas Safe registered person
All gas tightness testing must be carried out by a Gas Safe registered engineer. It is a criminal offence for an unregistered person to carry out any gas work, including tightness testing. The test record must include the engineer's Gas Safe registration number.
4. Frequently Asked Questions
What is the test pressure for domestic cold water systems?▾
1.5 times the maximum operating pressure. For a typical domestic cold water system operating at 3 bar, the test pressure is 4.5 bar. The test must be held for a minimum of one hour with no measurable pressure drop.
Can plastic pipework systems be air tested?▾
Some plastic pipework systems can be air tested, but only where the manufacturer's instructions and the applicable standard permit it, and a suitable risk assessment has been carried out. Air testing carries additional risks because air is compressible — a failure under air pressure releases energy more violently than a failure under water pressure.
What does WRAS approval mean?▾
WRAS (Water Regulations Advisory Scheme) approval confirms that a product or fitting has been tested and found to comply with the Water Supply (Water Fittings) Regulations. It provides assurance that the product will not contaminate drinking water through leaching, taste, odour, or microbial growth.
What records must a Gas Safe engineer provide after gas work?▾
A Gas Safe registered engineer must provide a Gas Safety Record (tightness test confirmation), a Tightness Test Record (documenting the test method and result), and a Commissioning Record for each gas appliance installed. These records must be provided to the client and retained by the installing company.
Generate your Pressure Test Record on Construction Suite
Construction Suite walks you through every required section with a guided Q&A — built to BS EN 806 / Gas Safety Regs — and generates a professionally formatted document in minutes.
Get started freeThis guide is for general informational purposes only and does not constitute legal advice. While every effort is made to ensure accuracy, regulations change and individual project circumstances vary. Construction Suite is a trading name of Xzist Digital Ltd, registered in England and Wales.
